IEL d.o.o.
HR

ZELK-2 Arc Protection Device

Fast optical arc detection device with up to 6 optical probes and trip output without intentional delay.

ZELK-2 detects electric arcs in switchgear and activates the circuit breaker without intentional delay. Optical arc detection and a static trip element give a very short operating delay compared with the breaker opening time, helping detect the arc at its earliest stage and reduce possible damage in the installation.

  • Sub-1 ms operation

    The static trip element provides an operating delay below 1 ms.

  • Up to 6 optical probes

    Probes are installed in optically separated switchgear compartments and aimed at possible arc locations.

  • Local fault indication

    A numeric display shows and stores the number of the probe that detected the arc.

  • Remote signalling

    Loss of supply and protection operation are signalled remotely with one or two signalling relays, depending on the selected version.

  • SM, IM and ZPM integration

    In selective systems it can operate with the SM current module, IM trip module and breaker-failure protection module.

  • DIN-rail mounting

    Compact housing for mounting on a DIN EN 50022-35 rail or on a wall.

Optical inputs

Number of probes
max. 6
Probe cable length
4, 7 or 10 m; other lengths on request, maximum 20 m

Electronic inputs and outputs

SM input
galvanically isolated, 12 V / 20 mA
Outputs for IM, ZPM and ZELK-2
open collector, 12 V / 20 mA

Trip element

Trip current
10 A for 300 ms
Minimum load current
5 mA
Maximum voltage
600 V DC
Rated voltage
220 V AC or DC
Operating delay
< 1 ms

Signalling

Remote signalling
1 or 2 signalling relays; 220 V AC, 300 V DC, 5 A; K1 NC, K2 NO contact
Local signalling
green power LED and numeric fault-location display

Power supply

Supply voltage
24, 48, 110 or 220 V DC +40% / -20%; or 220 V AC +10% / -20%
Consumption
standby 3.6 VA, max. 5 VA
Operation after supply loss
approx. 250 ms

General

Temperature range
-10...+55 °C
Insulation
2.5 kV, 50 Hz, 1 min between all galvanically isolated circuits
Mounting
DIN EN 50022-35 rail or wall
Dimensions
100 x 74 x 120 mm
  • DIN EN 50022-35
  • Insulation 2.5 kV, 50 Hz, 1 min

Related products

ZELK-3 device, terminal block and OS optical probes

ZELK-3

Arc protection for a larger number of probes and non-selective or sectional configurations.

View details
SM current module

SM

Current condition module for higher availability of the arc protection system.

View details
IM trip module

IM

Fast trip-contact multiplier for operating multiple breakers.

View details