IM Trip Module
Trip module that multiplies fast trip contacts in an arc protection system.
The IM trip module is used as a fast contact multiplier in an arc protection system. When the output of a ZELK-2 or ZELK-3 protection device must operate several incoming energy paths, IM enables simultaneous operation of up to five breakers in the switchgear installation.
-
Up to 5 trip elements
Version with 2 to 5 static trip elements for operating multiple breakers.
-
No auxiliary supply
The IM module does not require a separate auxiliary power supply.
-
Galvanically isolated outputs
Trip elements are galvanically isolated from the ZELK input and from each other.
-
AC/DC trip circuits
Breaker trip circuits can be supplied by DC or AC voltage.
-
Sub-1 ms operation with ZELK
The operating delay of the IM + ZELK combination is below 1 ms.
- Input for ZELK-2/ZELK-3
- 12 V / 20 mA
- Number of trip elements
- 2 to 5
- Trip current
- 10 A for 300 ms
- Minimum load current
- 5 mA
- Maximum voltage
- 600 V DC
- Rated voltage
- 220 V AC or DC
- IM + ZELK operating delay
- < 1 ms
- Temperature range
- -10...+55 °C
- Insulation
- 2.5 kV, 50 Hz, 1 min between all galvanically isolated circuits
- Mounting
- DIN EN 50022-35 rail
- Dimensions
- 45 x 74 x 120 mm
Electronic input
Trip elements
General
- DIN EN 50022-35
- Insulation 2.5 kV, 50 Hz, 1 min