IEL d.o.o.
HR

Fault Indicator IK-40

Modular fault indicator for local and remote supervision of earth and short-circuit faults in MV cable and overhead networks.

The IK-40 fault indicator has up to four independent fault indication modules. It connects to LPCT or SS-10/SS-20 current sensors and LPVT voltage sensors, samples currents and voltages, and runs algorithms for local and remote fault detection, indication and recording.

  • Modular design

    Up to 4 fault indication modules enable use across multiple feeder bays.

  • Current and voltage sensors

    Supports LPCT, SS-10 and SS-20 current sensors as well as LPVT voltage sensors.

  • Directional detection

    Algorithms cover ANSI 50/51, 50N/51N, 67/67N, 27, 47, 59/59N, 21YN and 32N.

  • Fault record registration

    Combined with UST-10Gc, it supports COMTRADE fault record registration.

  • USB and remote parameterization

    Settings can be configured locally via USB, remotely, or with IK Dialog software.

Modules and inputs

Number of IK modules
up to 4
Current inputs per module
3(4), 2x SS-10 and 1x SS-20 or LPCT
Voltage inputs per module
3(4), 3 x LPVT, 3.25 sqrt(3)

Fault indication functions

Phase and earth-fault currents
I>>, I>, Iphi>: 50...800 A; Io>>, Io>, Iophi>: 2...200 A; times 0.04...60 s
Directional and voltage functions
ANSI 32N, 21YN, 21FL, 27, 47, 59 and 59N
MV network types
isolated, resistance-earthed, Petersen-coil earthed and solidly earthed networks
2nd harmonic detection
inrush current

Signalling and communication

Fault signalling
2 multi-colour LEDs Io and I>> per module plus 1 multi-colour comm LED
Measurement
4I, 4U, P, Q, S, f, cos phi per module
Communications
RS485 or optional fibre optic, USB; MODBUS RTU or optional IEC 60870-5-101

General

Power supply
48 V DC +/-15%, 8 VA
Reset
voltage reset, timed reset 2...96 h, manual push-button reset; reset active or inactive
Dimensions and mounting
94 x 94 x 90 mm, mounting on 35 mm DIN rail
Temperature range
-25 to +55 °C
  • HRN EN 60255-151
  • ANSI 50/51, 50N/51N, 67, 67N, 32N, 21YN, 21FL, 27, 47, 59, 59N
  • MODBUS RTU
  • IEC 60870-5-101 as option
  • HRN EN 60068-2-1 and HRN EN 60068-2-2
  • HRN EN 60255-27