Directional fault indicator for detection, indication and recording of earth and short-circuit faults in MV overhead networks.

The IK-20 fault indicator uses NS-20 voltage sensors and SS-30 current sensors for local and remote fault detection in MV overhead networks. The device indicates fault type and direction on LCD and LED displays and can send data to the control centre via GSM/GPRS, radio modem or DT-20RN remote terminal.

  • Short-circuit and earth-fault detection

    Supports ANSI functions 50, 51, 67, 50N, 51N and 67N, plus transient analysis for directional earth-fault detection.

  • Non-conventional sensors

    Works with NS-20 capacitive voltage sensors and SS-30 inductive current sensors mounted on the disconnector.

  • Local and remote signalling

    Fault type and direction are indicated locally on LCD/LED displays and relay outputs and remotely through the communication system.

  • Automatic sectioning

    Combined with UST-10Gc, it enables automatic network sectioning and selective fault isolation during the dead time.

  • Simple parameterization

    Pickup currents, reset mode and time, and operating times are configured via LCD and keypad or by notebook computer.

Sensor inputs

Current inputs
3 inputs, SS-30 current sensors
Voltage inputs
6 inputs, NS-20 capacitive sensors
Measurement and digital inputs
2 measurement inputs M1/M2 and 4 digital inputs as options

Fault indication functions

Phase currents
I>>, I>, Iphi>: 50...800 A, 1 A step; times 0.04...60 s
Earth fault
Io>>, Io>, Iophi>: 2...200 A, 0.1 A step; times 0.04...60 s
Transient earth fault
2...200 A, 0.1 A step; analysis within 120 ms

Signalling and communication

Fault signalling
4 two-colour LEDs, illuminated 2x16 LCD and 4 programmable relay outputs
Communication
RS485 or fibre-optic communication; MODBUS RTU or IEC 60870-5-101

General

Power supply
230 V AC +10%/-20% or 24, 48, 110, 220 V DC +45%/-20%, max. 5 VA
Reset
voltage reset, timed reset 2...96 h or manual push-button reset
Dimensions
96 x 96 x 90 mm
Temperature range
-25 to +55 °C
  • ANSI 50, 51, 67, 50N, 51N, 67N
  • MODBUS RTU or IEC 60870-5-101
  • EN 60255-5
  • EN 61000-6-2 and EN 61000-6-4