IEL d.o.o.
HR

Fault Indicator IK-10

Fault indicator for local and remote supervision of earth and short-circuit faults in cable substations, up to 4 feeders.

The microprocessor-based IK-10 fault indicator uses SS-10 and SS-20 current sensors to supervise MV feeder bays in 10(20)/0.4 kV cable substations. It registers the fault before protection trips, indicates fault type and location locally by LEDs, and supports the external SL-10 signal lamp and remote communication.

  • Up to four feeders

    One IK-10 can supervise up to 4 feeders and detect earth and short-circuit faults per feeder.

  • Two Io measurement arrangements

    Arrangement A uses three SS-10 sensors for Io >= 20 A, while arrangement B combines SS-10 and SS-20 for Io >= 5 A.

  • Local and external indication

    Eight device LEDs and the optional SL-10 signal lamp enable quick fault recognition.

  • Remote supervision

    Connection to UST-10Gc, GSM/GPRS or radio modem enables economical remote fault supervision and network reconfiguration.

  • Uninterruptible supply

    A connected VRLA battery can provide the device with its own uninterruptible supply.

Sensor inputs

Number of sensor inputs
12 I>> or 8 I>> + 4 Io
Sensor input type
SS-10(20) current sensors

DIP switch parameterization

ANSI 50
I>>: 225, 450, 575, 700 A
ANSI 51N
Io>: 5...160 A; to>, t>>: 40, 100, 200, 350 ms

IK Dialog parameterization

Phase currents
I>>, I>: 50...800 A, 1 A step; times 0.04...60 s
Earth fault
Io>>, Io>: 5...200 A, 1 A step; times 0.04...60 s

Signalling and communication

Fault signalling
8 LEDs and external SL-10 LED signal element
Relay outputs
8 optional relays, normally open contact 250 V, 5 A
Communication
RS485 or fibre optic, MODBUS RTU

General

Power supply
230 V AC +10%/-20% or 24, 48, 110, 220 V DC +45%/-20%, max. 8 VA
Indication reset
voltage reset, timed reset 2...96 h, manual push-button reset; reset active or inactive
Dimensions
96 x 96 x 90 mm
Temperature range
-25 to +55 °C
  • ANSI 50, 51, 50N, 51N
  • MODBUS RTU
  • IEC 60870-5-104
  • EN 60255-5
  • EN 61000-6-2 and EN 61000-6-4
  • DIN 43700