Overcurrent Relay NR-200S
A multifunction numerical overcurrent relay for protection of medium-voltage and low-voltage networks. It integrates overcurrent, earth fault and breaker failure protection, with additional optional protection functions.
A multifunction numerical overcurrent relay for protection of medium-voltage and low-voltage networks. It integrates overcurrent, earth fault and breaker failure protection, with additional optional protection functions.
-
ANSI 50 and ANSI 51 overcurrent protection
-
ANSI 50N and ANSI 51N earth fault protection
-
ANSI 51BF breaker failure supervision
-
Optional ANSI 49 thermal protection
-
Optional ANSI 46BC broken conductor protection
-
True RMS current measurement
-
2x16 LCD and multicolor LED signalling
-
RS485, optical or Ethernet communication
- Current inputs
- 1 A or 5 A
- Frequency
- 50/60 Hz
- Burden
- <0.2 VA
- Withstand
- continuous 4 x In, 5 s 40 x In, 1 s 100 x In
- ANSI 50
- 3 stages, I>, I>>, I>>>
- ANSI 51
- inverse-time stage IIT
- ANSI 50N
- 2 earth fault stages, I0>, I0>>
- ANSI 51N
- inverse-time earth fault stage I0IT
- ANSI 51BF
- breaker failure supervision
- ANSI 49
- thermal overload protection option
- ANSI 46BC
- broken conductor protection option
- Display
- LCD 2x16, 5 dual-color LEDs
- Relay outputs
- 3 + 1 programmable, 2 additional programmable outputs option
- Communication
- RS485 MODBUS RTU, optical option, Ethernet MODBUS TCP / IEC 61850 option
- Supply
- 230 V AC or 24/48/110/220 V DC
- Temperature range
- -25 C to +60 C
- Mounting
- panel, DIN 43700
- Dimensions
- 96 x 96 x 90 mm
- MODBUS RTU
- MODBUS TCP (option)
- IEC 61850 (option)