KON-50 Meter Protocol Converter
Protocol converter for communication integration of electronic meters with measurement and supervision systems.
The KON-50 electric energy meter protocol converter connects electronic meters with measurement and supervision systems using different communication protocols. The input line supports IEC 62056-21 or IEC 61107, while output lines can use MODBUS RTU, IEC 60870-5-101, IEC 60870-5-104 or MODBUS TCP.
-
Meter protocol conversion
Connects IEC 62056-21 or IEC 61107 meters to supervision systems.
-
Up to three communication lines
Supports the meter input line and up to two separate lines towards measurement and supervision systems.
-
Multiple SCADA protocols
Output lines can use MODBUS RTU, IEC 60870-5-101, IEC 60870-5-104 or MODBUS TCP.
-
Multiple communication media
RS232, RS485, optical, Ethernet and GSM/GPRS media are available.
- Line 1
- IEC 62056-21 or IEC 61107, RS485 medium
- Line 2
- standard MODBUS RTU over RS485
- Line 3
- optional, standard MODBUS RTU over RS485
- Optional protocols
- IEC 60870-5-101, IEC 60870-5-104, MODBUS TCP, others on request
- Optional media
- RS232, G.F.O., P.F.O., Ethernet, GSM/GPRS
- Supply voltage
- 24, 48, 110 or 220 VDC +45% -20%; 110 or 230 VAC +10% -20%
- Power consumption
- <3 VA
- Dimensions
- 106 x 90 x 60 mm
Communication
Supply and installation
- IEC 62056-21
- IEC 61107
- MODBUS RTU / MODBUS TCP
- IEC 60870-5-101 / IEC 60870-5-104